ITI provides training and resources for overhead inspection and maintenance
Regulation
National Electrical Code (NEC) NFPA 70 - Article 610, Cranes and Hoists
Table 610.14(A) shows the allowed ampacity of power cables and a reduction factor if the ambient temperature is more than 86-deg F.
National Electrical Code (NEC) NFPA 70 - Article 310, Conductors for General Wiring
Table (310.15(B)(16) for power cables, but the allowed ampacity is smaller than in article 610. (Article 610 is preferable).
In Article 310 is also the ampacity chart for multiconductor cables and a derating chart for the number of wires in the cable.
Note: Most electrical cable manufacturers provide the NEC charts at the end of their catalogs. This is probably the easiest way to find the information you are looking for.
Best Practice
- If this is a wire replacement, use the same size that is currently installed installed.
- Check the crane manual and spare part list. Look for the specifications of the cables to be replaced.
- If you work with a supplier or distributor, ask them for a recommendation and a quote.
Tip: Find out more about ITI's inspection training opportunities at ITI Crane Inspection.
Disclaimer: The information provided above: (i) is intended only as a general educational resource for Users of our Knowledge Base, and is not intended for a specific use in, and does not constitute advice for, a User’s specific situation; and (ii) may no longer be accurate as of the date of a User’s access due to unforeseen changes to regulations, standards or other factors. By accessing our Website and Knowledge Base, you acknowledge and agree that you are solely and exclusively liable and responsible for your actions arising out of the Website and Knowledge Base, and ITI shall have no liability or responsibility therefore.